1 HVAC PLAN

7 downloads 1513 Views 528KB Size Report
3 Jun 2011 ... VTU-12-1. A 320. VTU-12-2. 5A 150. 2B 315. B 100. B 270. 4B 390 ... MATCHLINE M3.1.1.6. MATCHLINE M3.1.1.5. MATCHLINE M3.1.1.5.
GENERAL NOTES

FABRICATED HEAT CAPTURE HOOD LOCATED OVER LUCIFER FURNACE AND OIL QUENCHING BATH. SEE DETAILS FOR CONSTRUCTION INFORMATON.

4

36x36 OA DUCT W/ MOTORIZED DAMPER UP TO RGV-CO1 ON ROOF. UPON CO SENSOR GOING INTO ALARM DAMPER SHALL OPEN AND EMERGENCY EXHAUST FANS SHALL ENERGIZE.

1. ALL EXPOSED DUCTWORK SHALL BE ROUND SPIRAL DOUBLE WALL CONSTRUCTION.

2

CO - CARBON MONOXIDE SENSOR. MOUNT AT 60" AFF. PROVIDE 3M MARCURCO CM-6 PROGRAMMABLE SENSOR AND ASSOCIATED MOUNT KIT AND RELAYS NEEDED FOR FAN CONTROL.

5

COORDINATE LOCATION OF WALL MOUNTED AC UNIT ABOVE DOORWAY. ROUTE PUMPED 1" CONDENSATE TO FLOOR DRAIN IN CUSTODIAL 011.

6

2. COORDINATE DUCT MAINS BETWEEN STRUCTURAL JOISTS WHERE NECESSARY. DUCT TAKEOFFS SHALL BE ROUTED BETWEEN STRUCTURAL JOIST WEBBING.

PROVIDE SMOKE DAMPER AND DUCT MOUNTED SMOKE DETECTOR IN TRANSFER DUCT.

3

COORDINATE LOCATION OF WALL MOUNTED AC UNIT ABOVE DOORWAY. ROUTE PUMPED 1" CONDENSATE TO FLOOR DRAIN IN MECHANICAL ROOM 013.

1

2-2

2.3-2

3-2

4-2

ARCHITECTURE

1-2

FAWLEY BRYANT ARCHITECTS, INC. 1001 MANATEE AVE. W. BRADENTON, FL 34205 PH. 941.750.0009 FX. 941. 749.5747 www.fawley-bryant.com

1

INTERIORS PLANNING

KEYED NOTES

FAWLEY BRYANT

KEYED NOTES

20"x20"

ENGINEERING

UP TO EF-21

A

5C 210 18"ø

16"ø

12"ø

10C250

VTU-13-4

VTU-14-3 A

D5000

12"x6"

90 12"ø

12"x6"

16"ø

20"ø

14"ø

4D 475

UP TO EF-24

18"ø 14"ø

UP TO EF-20

D 240

12"x12"

LAB 500

12"x12"

4224 SF

12"x6"

22"ø

20"ø

18"ø

16"ø

D5000

10C250

VTU-13-3

5C 210

16"ø

12"ø VTU-14-2

LAB 400

6"ø 12"x6"

T

14"ø

VTU-13-2

T

504 49 SF

D

12"ø

T

12"ø

PLANNING

2B 315

502

6"x6" 75

D

75 6"x6" FLAMMABLE

STORAGE 503

90 12"x6"

A 165

628 SF

18"x36"

VTU-14-1 A

167 SF

2A 125

5C 210

16"ø

B 145TEACHER

10"ø

VTU-13-1

5A 140 LAB 501 679 SF

STORAGE

26"ø

49 SF

48"x18"

75

A

14"x12"

STORAGE

50

502A 86 SF

D3400

24"x20"

506

44"x20"

C

T

46 SF

10"ø

D

T

VTU-14-14 C 500 COVERED WALKWAY 099

6

010

1 M5.1.6

248 SF

8968 SF

1 0

104 SF

B

A 300281 SF

0

10"x10"

5

28"x20"

CUSTODIAL

013

18x18 UP TO RGV-13

55 SF

1

2

B

COMMUNICATIONS CLOSET

607

2B 225

013B

20x20 UP TO RGV-12

14"x14"

AHU-12

MATCHLINE 1 / A3.1.1.6 M3.1.1.6 1 / A3.1.1.4 M3.1.1.5 MATCHLINE

3

UP TO EF-17

203 SF

2B 315 VTU-14-4

6

A

14"x14" 90

U

4B 390

16"x16"

LAB 402

5A 330

12"x12"

VTU-12-1

14"ø

STORAGE

A 320

1 / A3.1.1.5

22"x20"

605

A 100 604

346 SF

195 SF

712 SF

A 150

B 150

14"x14"

6"x10"

404 348 SF

A 150

22"x16" 10"x12"

D-2

16"x14"

LAB

12"x12"

603

UP TO SF-2

757 SF

16"x16" 12"ø

U

10"x12" 20"x18" 5A 150

MATCHLINE M3.1.1.5 MATCHLINE M3.1.1.4

8"x10"

2B 315

VTU-12-2

A

50 STORAGE

4A 170

U

UP TO SF-1

304

"To the best of the Architect's or Engineer's knowledge, the plans and specifications comply with the applicable minimum building codes and applicable fire safety standards as determined by local authority in accordance with Chapter 553 and 663 of Florida Statutes."

100 SF

30"x14" UP TO EF-19

B 110

20"x18"

T

B 500

14

30"x14"

12"x12"

15

04.29.11 06.03.11

STORAGE

403

VTU-14-7

16"x14"

VOCATIONAL 24"x18" FITTING ROOM

B 150

CLASSROOM

24"x18"

28"x18"

B 500

14"x14"

ASI #1 ASI #3

12"x10"

14"x12"

A 150

30x30 UP TO RGV-14

50

76 SF

4A 175

928 SF

24"x24"

FLAMMABLEA STORAGE

1 2

405

28"x20"

012

AC-7

24"x24"

0

12"ø

WOMENS RR

1 / A3.1.1.4

16

Construction Documents

17

HVAC PLAN 1 6/3/2011 3:31:02 PM

C:\Documents and Settings\kevin.peterson\My Documents\710003 Mech Central-MTI Caruso Road_Kevin.peterson.rvt

Revisions:

8"x10"

1

606

10"x10"

VTU-14-5

2336.8 KJP JMH 02.14.11

T

B

OVEN ROOM 172 SF

8"ø UP TO EF-26

T

0

110 SF

Project No. Drawn By Checked By Date

4D 475

VTU-14-6

44 SF

AHU-14

U

STORAGE

011

1267 SF

10"ø

B 100

MECHANICAL ROOM

12"x12"

12"ø

12"ø

AC-8 D 500 EF-31

20"ø

12"x6"

16"ø

401

199 SF

2B 225

3C 210

TEACHER PLANNING

IDF ROOM 009

B

UP TO EF-25

B 270

001B

MENS RR

013A

AHU-13

CORRIDOR

U

A 150 ELECTRICAL ROOM

134 SF

C-2

2

44"x20"

FLAMMABLE 6"x6" STORAGE

16"x20"

10"ø

14"x12"

U

505 8"x8"

D

D5000

16"x14"

B 190

FLAMMABLE STORAGE EF-16

G

20"x20"

4

24"ø

14"ø

2

18"x36"

UP TO EF-23

7209 SF 12"ø

12"x6"

UP TO EF-16 ON STORAGE ROOF

B-2

UP TO EF-22

First Floor - Wing 3 (Cont.) - Mechanical

10"ø

18"x36" 20"x20"

State Road 70

20"ø

Manatee Technical Institute State Road 70 Campus

22"ø

Phone: 813-637-0110 Fax: 813-637-0013 F O R A R C H I T E C T U R E www.tlc-engineers.com © Copyright 2010 TLC Engineering for Architecture, Inc. EB#0000015 TLC NO: 710003

500 N. Westshore Blvd. Suite 435 Tampa, Florida 33609

A-2

1/8" = 1'-0"

M3.1.1.5 Originals printed @ 24" x 36" scale as required All rights reserved c 2010