Description Technical data Applications Tests

39 downloads 69 Views 446KB Size Report
Description. • In conformity with standards NF S 61-213/CN and NF EN 14384. • NF quality brand for French market. • High performances: - Low operating torque  ...
PILLAR FIRE HYDRANT WITH PROTECTING HOOD “EMERAUDE” and “EMERAUDE CHOC DN 100” - Series A1 10 and A1 15

Non-freezing pillar fire hydrant with protecting hood, for the connection above ground of the mobile equipment of fire protection services.

Description • In conformity with standards NF S 61-213/CN and NF EN 14384. • NF quality brand for French market. • High performances: - Low operating torque, - Bubble tight shut-off, - Non-freezing type, - Traffic type (Choc version), avoiding leakage in case of impact. • Design: - Symmetric outlets, in conformity with NF E 29-572 French standard. Other models on request, - Clockwise closing direction (CC), - Anti-water hammer and anti-vibrations main valve guide, enabling progressive opening/closing, - Thick main valve with elevated seat, easing the watertightness in presence of foreign matters, - Duck foot bend with loose flange with space requirement according to EN 545, - Automatic drainage device that can be inspected without digging, with protective tube. • Anticorrosion protection: - By internal and external epoxy coating by cataphoresis, - Composite hood, corrosion resistance, with coating insensitive to Ultraviolet radiation, in conformity with NFX 08-008 standard.

Technical data • Range : DN 100 and DN 100 traffic type. Also available in DN 65, 80, 150. • Maximal working pressure: PN 16. • Seating: rate 3 according to NF E 29-311 standard. • Connection flanges drilling according to standards EN 1092-2 and ISO 7005-2: ISO PN 10/16.

Applications • Fire protection networks (according to EN 1074-6 standard).

Tests • Fully tested manufacturing.

• Ease of installation: - Height adjustable hood up to 100 mm, - Rotated head through 360°, degree by degree, without digging, - Installation height adjustment by specific short length pipes: 0.05m, 0.15m and 0.25m to be installed between seat and duck foot. • Simple and easy to use: - Interdependant doors and base, - 1/4 turn opening with lateral opening without effort, - Total clearance of the outlets, - Operation with 30x30 square operating nut and handweel. • Maintenance: - Easy dismantling of the main valve, - Interchangeability of the inner components with previous models, - Heighten kit after installation 0.20m, - Drainage can be replaced without digging, - Repair kit for Traffic type “Mini kit choc”, enabling fast and safe repair. • Options: - Personalization, - Safety square, - Other height adjustment, - Straight connection, - Other outlet.

The technical data and performance can be modified without prior notice depending on the technical evolution

HZIT03-11-111B-EN

PILLAR FIRE HYDRANT WITH PROTECTING HOOD “EMERAUDE” and “EMERAUDE CHOC DN 100” - Series A1 10 and A1 15

Series A1 10 - “Emeraude” 29

A

1

28

2

27

3

a

26 30

D

25 24

7

E

B

4 5 6

23

8

b

b

31 32 Ground

33

22 21

9

19 18

b±5°

75°

130°

C

20

10

a±5°

17

11 12

16 DN

13 2

14

15

F Item

Designation

Qty

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

ø 165 handwheel (+ screw + washer) Packing box (+ gaskets) Head without nozzle DN 65 symmetric nozzle DN 65 symmetric nozzle cap without air inlet check valve DN 65 symmetric nozzle cap with air inlet check valve Hinge Locking nut Drainage tube Hydraulic evacuation sub set which can be inspected Drainage body Protective tube DN 100 main valve (+screw) DN 100 duck foot bend with loose flange O-ring DN 100 seat O-ring DN 100 main valve Command sub set: Tube Valve holder Stem nut 20 Lower barrel 21 Support plate 22 O-ring 23 1/2 flange 24 DN 100 symmetric nozzle 25 DN 100 symmetric nozzle cap 26 Lock sub set 27 O-ring 28 Operating stem (+1/2 ring) 29 Bonnet 30 Door with lock 31 1/2 front base 32 1/2 rear base 33 Door without lock 34 Bolts Drawing and part list corresponding to model Emeraude n° 4/1.00 m Type A

DN

Emeraude n° 4/1,00 m n° 4/1,20 m

100 100

1 1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 2 1 1 1 1 1 1 1 1 1 1 -

Materials

Standards

Cast iron/EN-GJL-250 Brass/CuZn36Pb2As Ductile iron/EN-GJS-450-10 Alu-silicium/EN-AC-AI-SI7Mg0.6 Alu-silicium/EN-AC-AI-SI7Mg0.6 Alu-silicium/EN-AC-AI-SI7Mg0.6 Steel/X2CrNi18-09 Galvanized steel ABS – Copper alloy/CuZn36Pb2As ABS Cast iron/EN-GJL-250 Ductile iron/EN-GJS-450-10 Elastomer/EPDM Ductile iron/EN-GJS-450-10 Elastomer/EPDM Elastomer/EPDM Galvanized steel/S-235 Cast iron/EN-GJL-250 Copper alloy/CuZn39Pb2 Ductile iron/EN-GJS-450-10 ABS Elastomer Ductile iron/EN-GJS-450-10 Alu-silicium/EN-AC-AI-SI7Mg0.6 Alu-silicium/EN-AC-AI-SI7Mg0.6 Copper alloy/CuZn39Pb2 Elastomer/EPDM Copper alloy/CuZn39Pb3 Cast iron/EN-GJL-250 Composite Composite Composite Composite Stainless steel – galvanized steel

EN 1561 EN 12164 EN 1563 EN 1706 EN 1706 EN 1706 EN 10088

A mm

B C mm mm

D E mm mm

F Torque Nominal flow rate Nb of turns mm m3/h for closing

350 350

800 800

500 500

180 180

1000 1200

600 600

Level 1 Level 1

60 60

13 13

EN 12164 EN 1561 EN 1563 EN 681-1 EN 1563 EN 681-1 EN 10025 EN 1561 EN 12165 EN 1563

EN 1563 EN 1706 EN 1706 EN 12165 EN 12164 EN 1561

Nb of outlets 1x100 + 2x65 1x100 + 2x65

The technical data and performance can be modified without prior notice depending on the technical evolution

Outlets Kv Weight Kg

DN 100 DN 65

190 190

110 110

85 96

HZIT03-11-111B-EN

Series A115 - “Emeraude Choc”

PILLAR FIRE HYDRANT WITH PROTECTING HOOD “EMERAUDE” and “EMERAUDE CHOC DN 100” - Series A1 10 and A1 15

31

1

30

2

29

a

28

32 37

25

35

E

33 34

D

27 26

8

Ground A

23

9

b

b

36

24

7

B

3 4 5 6

22

a±5°

b±5°

75°

130°

21

10

20

12

19

13

18

C

11

7 9

8

17 DN

14 15

20

16 Choc system

F Item

3

Designation

Qty

1 2 3 4 5 6 7

Handwheel 1 Packing box (+ gaskets) 1 Head without nozzle 1 DN 65 symmetric nozzle cap without air inlet check valve 1 DN 65 symmetric nozzle 2 DN 65 symmetric nozzle cap with air inlet check valve 1 Upper command sub set: Stem 1 FF coupling 1 MF coupling 1 8 Equipped stem holder 1 9 Operating stem (+1/2 ring + 30x30 operating nut) 1 10 Drainage tube 1 11 Hydraulic evacuation sub set which can be inspected 1 12 Drainage body 1 13 Protective tube 1 14 DN 100 main valve 1 15 DN 100 duck foot bend with loose flange 1 16 O-ring 1 17 DN 100 seat 1 18 O-ring 1 19 DN 100 main valve 1 20 Lower command sub set: Tube 1 Valve holder 1 Stem nut 1 21 Lower barrel 1 22 Support plate 2 23 Breaking bolt 4 24 O-ring 1 25 1/2 flange 2 26 DN 100 symmetric nozzle 1 27 DN 100 symmetric nozzle cap 1 28 Lock sub set 1 29 O-ring 1 30 Upper operating rod (+1/2 ring) 1 31 Bonnet (+guide) 1 32 Door with lock 1 33 Hinge 2 34 Locking nut 1 35 1/2 front base 1 36 1/2 rear base 1 37 Door without lock 1 38 Bolts Drawing and part list corresponding to model Emeraude n° 4 Choc/1.00 m. Type C

DN

Emeraude n° 4 choc/1,00 m n° 4 choc/1,20 m

100 100

A mm

B C mm mm

D E mm mm

F mm

350 350

800 800

500 500

180 180

1000 1200

600 600

Materials

Standards

Cast iron/EN-GJL-250 Brass/CuZn36Pb2As Ductile iron/EN-GJS-450-10 Alu-silicium/EN-AC-AI-SI7Mg0.6 Alu-silicium/EN-AC-AI-SI7Mg0.6 Alu-silicium/EN-AC-AI-SI7Mg0.6 Galvanized steel/S-235-JR Ductile iron/EN-GJS-450-10 Ductile iron/EN-GJS-450-10 Ductile iron/EN-GJS-450-10 Copper alloy/CuZn39Pb3 ABS – Copper alloy/CuZn36Pb2As ABS Cast iron/EN-GJL-250 Ductile iron/EN-GJS-450-10 Elastomer/EPDM Ductile iron/EN-GJS-450-10 Elastomer/EPDM Elastomer/NBR Galvanized steel/S-235-JR Cast iron/EN-GJL-250 Copper alloy/CuZn39Pb2 Ductile iron/EN-GJS-450-10 ABS Steel/ steel A2 Elastomer/EPDM Ductile iron/EN-GJS-450-10 Alu-silicium/EN-AC-AI-SI7Mg0.6 Alu-silicium/EN-AC-AI-SI7Mg0.6 Copper alloy/CuZn39Pb2 Elastomer/EPDM Copper alloy/CuZn39Pb3 Cast iron/EN-GJL-250 Composite Steel A2/X2CrNi18-09 Galvanized steel Composite Composite Composite Stainless steel – galvanized steel

EN 1561 EN 12164 EN 1563 EN 1706 EN 1706 EN 1706 EN 10025 EN 1563 EN 1563 EN 1563 EN 12164

Torque Nominal flow rate Nb of turns m3/h for closing Level 1 Level 1

60 60

13 13

EN 12164 EN 1561 EN 1563 EN 1563 EN 681-1 EN 10025 EN 1561 EN 12165 EN 1563 EN ISO 3506 EN 1563 EN 1706 EN 1706 EN 12165 EN 12164 EN 1561 EN 10088

Nb of outlets 1x100 + 2x65 1x100 + 2x65

The technical data and performance can be modified without prior notice depending on the technical evolution

Outlets Kv Weight Kg

DN 100 DN 65

190 190

110 110

88 104

HZIT03-11-111B-EN

PILLAR FIRE HYDRANT WITH PROTECTING HOOD “EMERAUDE” and “EMERAUDE CHOC DN 100” - Series A1 10 and A1 15

Installation HEIGHT

ADJUSTABLE HOOD

100 mm

Surface pavement

SURFACE

Anchorage base Concrete bloc 500x500 Minimum thickness 15 cm. Surface 5° slope.

BOX

MINIMUM

MAXIMUM

EXTENSION OPERATING SET

“S” FITTINGS FOR ADJUSTMENT

Dry stones for drainage

Outlets clearance SOFT

485

SEALING GATE VALVE

Concrete bloc A

MAJOR STOP

R5

4

00

Maximum opening of the doors

250

The installation plan here above is in conformity with the NF S 62-200 French standard. Installation height adjustment by specific short length pipes, to be installed between seat and duck foot. “S” fittings for adjusting at ground level between 0.5 and 1.5 m – DN 60/65, 80, 100, and 150. Repair kit for traffic type “Mini kit choc”, enabling fast and safe repair. Protection barrier respecting the standardized space requirement. Non-standard freeze-proof height, please consult us. Non-standard connection height, please consult us.

100

• • • • • • •

R5

00

DN

65

80

100

150

A mm

240

280

280

320

Opening of the doors for a pillar fitted at 100 mm from a wall

Options and accessories Safety square (Patented)

Personalization of the upper part

Short length pipe

“S” fittings with loose flanges

Protection barrier

Outlets/nozzles

0,05, 0,15 and 0,25 m. Installed between seat and duck foot

DN 65 to 150 Series A3 10

Series A3 40

According to ANSI B181-1-74 DN 2”1/2, 4”,4”1/2.

Outlets/nozzles

Outlets/nozzles

Outlets/nozzles

Outlets/nozzles

Heighten kit

According to BS 336 DN 3” et 4” with round thread

According to: DIN 14317, DN C 52 DIN 14318, DN B 75 DIN 14319, DN A 110

According to UNI 810 DN 45, 70, 100

According to UNE 23400 DN 45, 70, 100

After installation 0,2 m and operating set

Outlets/nozzles

According to BS 336 DN 2”1/2 instantaneous

Mini kit Choc

The technical data and performance can be modified without prior notice depending on the technical evolution