Power Balancing Control for Grid Energy Storage

0 downloads 0 Views 632KB Size Report
Hardware-In-Loop (HIL) Simulation is carried out. 24 to check the performance of the system and the PBC algorithm. Power circuit (comprises of. 25 inverter ...
1

Type of the Paper: Article

4

Power Balancing Control for Grid Energy Storage System in PV Applications - Real Time Digital Simulation Implementation

5 6

Sridhar Vavilapalli 1, Sanjeevikumar Padmanaban 2,*, Umashankar Subramaniam1, and Lucian Mihet-Popa3

2 3

Department of Energy and Power Electronics, School of Electrical Engineering, VIT University, Vellore, India ; [email protected]; [email protected] Department of Electrical and Electronics Engineering University of Johannesburg, Auckland, Johannesburg, South Africa ; [email protected] Faculty of Engineering, Østfold University College, Kobberslagerstredet 5, 1671 Kråkeroy; Building: S 316, Norway ; [email protected]

7 8 9 10 11 12 13 14

1

15 16

Academic Editor: name Received: date; Accepted: date; Published: date

17 18 19 20 21 22 23 24 25 26 27 28 29 30

Abstract: Grid energy storage system for PV Applications is connected with three different power sources i.e. PV Array, Battery and the Grid. It is advisable to have Isolation between these three different sources to provide safety for the equipment. The configuration proposed in this paper provides the complete isolation between the three sources. A Power Balancing Control (PBC) for this configuration is proposed to operate the system in three different modes of operation. Control of a dual active bridge (DAB) based battery charger which provides a galvanic isolation between batteries and other sources is explained briefly. Various modes of operation of a Grid energy storage system are also presented in this paper. Hardware-In-Loop (HIL) Simulation is carried out to check the performance of the system and the PBC algorithm. Power circuit (comprises of inverter, dual active bridge based battery charger, grid, PV cell, batteries, contactors and switches) is simulated and the controller hardware and user interface panel are connected as HIL with the simulated power circuit through Real Time Digital Simulator (RTDS). HIL simulation results are presented to explain the control operation, steady state performance in different modes of operation and the dynamic response of the system.

31 32

Keywords: Active power control; Battery charging; Dual Active Bridge; Energy storage system; hardware-in-loop

33 34

PACS: J0101

35

1. Introduction

36 37 38 39 40 41 42

In solar power plants, active power transfers from PV array to the grid during daytime and PV array loses its capability of generating power during night time or when the irradiation is weak. To supply power to the grid during night time also, energy storage is required. Since the power requirement during night time is much lesser than that of the daytime, energy storage with 25% of rated power of PV array may be selected for 24-hour operation. Block diagram of a grid energy storage system in a solar PV power plant is shown in Figure 1.

2

3

* Correspondence: [email protected]; Tel.: +27-79-219-9845

Energies 2016, 9, x; doi: FOR PEER REVIEW

www.mdpi.com/journal/energies

Energies 2016, 9, x FOR PEER REVIEW

GRID

2 of 14

PV ARRAY

TRANSFORMER PV-INVERTER

BATTERY CHARGER

BATTERY

43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71

Figure 1. Generalized block diagram of a Grid energy storage system in PV applications

Modes of operation of the above system are explained below. Mode1: During day time, PV Array feeds active power to the grid through an inverter and provides charging current to batteries through the Battery charger. Mode2: Battery is in charged condition and the PV array cannot feed full power to the grid i.e. during Partial clouds or during Night time or when irradiation is weak. In this mode of operation, PV array feeds the power based on Maximum power point (MPP) to the Grid and the batteries also feed active power to the grid. Mode3: Battery is in fully discharged state and the PV array cannot provide the charging current to the batteries i.e. during Night time. In this mode of operation, Grid provides the charging current to Batteries through Inverter and Battery charger. With such systems, it is also possible to charge the batteries from grid during non-peak load hours and the batteries along with PV array feed power to the grid during peak load hours. Since the system is connected with three different power sources i.e. PV array, battery and the grid, it is necessary to have isolation between these three power sources to provide safety for the equipment. Existing energy storage systems for PV applications using a Buck-Boost chopper based battery charger are briefly explained below. In configuration presented in [1], A DC-DC converter is connected between PV array and PV inverter and the battery is connected across DC Link as shown in Figure 2(a). In such systems, DC/DC converter needs to be designed for the maximum capacity of PV Array even though the battery capacity is very less when the system operates in Mode3, the Inverter should act like an active rectifier to charge the batteries and there is no isolation between PV array and the batteries. In the configuration shown in Figure 2(b), PV array and PV inverter are connected to the DC Link and battery is connected to the DC link through a Buck-Boost chopper. In this case, charger needs to be rated only for the rating of the battery. In the configuration presented in [2] and [3], Independent DC-DC converters are required to connect battery and PV array to DC link as shown in Figure 2 (c).

Energies 2016, 9, x FOR PEER REVIEW

= PV ARRAY

3 of 14

=

=

PV ARRAY

=

GRID

~

~ GRID

=

BATTERY

BATTERY

=

(a)

(b) DUAL ACTIVE BRIDGE

=

= PV ARRAY

~

= =

~

PV ARRAY

=

=

=

=

~

GRID

=

~

=

BATTERY

BATTERY

=

=

(d)

(c)

72

GRID

Figure 2. Various configurations of Buck-Boost Chopper based ESS for PV applications

73 74 75 76 77 78 79 80 81 82

An optimized operation of a Dual Active bridge (DAB) converter feeding a PV inverter connected to the grid is presented in [4] and [5]. Isolation between Grid and DC side is provided through high-frequency transformer used in DAB as shown in Figure 2(d). In such configuration, DAB needs to be designed for the full capacity of PV array. Since the design of DAB is complex for high power ratings, this configuration is more suitable for low power applications. There is no isolation between DC link and the power bank with this configuration also. From the above discussions, it is observed that Buck-Boost chopper based ESS cannot provide complete isolation. In this paper, DAB based ESS for PV applications is proposed to mitigate the drawbacks of Buck-Boost chopper based systems. The proposed system is explained briefly in the next section.

83

2 Dual Active Bridge based ESS for PV Applications

84 85 86 87 88

In this configuration, PV array and PV inverter are directly connected to the DC Link and the battery is connected to the DC link through a DAB based bi-directional battery charger as shown in Figure 3. High-frequency Transformer in DAB provides isolation between DC link and the power bank. A transformer connected between Inverter and grid provides Isolation between DC sources and AC Gird. INVERTER

=

PV ARRAY

GRID

~

=

~ =

~

BATTERY

DUAL ACTIVE BRIDGE

89

Figure 3. Dual Active Bridge based ESS for grid connected PV system

90 91 92

TRANSFORMER



Advantages of the proposed system are as given below. Battery charger needs to be designed only for the battery capacity.

Energies 2016, 9, x FOR PEER REVIEW

4 of 14

93 94 95 96



Independent controls for Battery charger and Inverter are possible.



When the system operates in Mode3, the Inverter acts like a Simple diode Rectifier and battery

97

2.1 Control of Dual Active Bridge based Battery Charger:

98 99 100 101 102 103 104 105 106 107 108 109 110 111

charger takes care of the charging current. •

High-frequency transformer in DAB provides isolation between PV array and the battery.

DAB based DC-DC converter consists of two H-Bridges and a high-frequency transformer. Source side H-Bridge is connected to the DC link and the load side H-bridge is connected to the battery as shown in Figure 3. High-frequency transformer is required to match battery voltage with the DC link voltage and also to provide isolation between PV array and the battery. Transformer’s leakage inductance helps in boost operation [6], [7]. The transformer winding connected to the Source side H-Bridge is considered as Primary and the winding connected to the Load side H-Bridge is considered as secondary. Control block diagram of a DAB based battery charger is shown in Figure 4. During Battery charging mode, the reference battery current is generated based on the state of charge (SOC) of the battery. During discharge mode, the reference battery current is generated based on the active power required for grid and maximum power point (MPP) of PV array. Source side and load side H-bridges act like a simple square wave inverter. Square pulses with 50% duty cycle are given to load side and source side H-Bridges. Power flow through DAB is controlled using phase shift control. The pulse generator provides the Gate pulses for source side and load side H-Bridges based on the phase shift obtained through PI controller. Grid Active Power Reference Pulse Generator

113

Load Side H-Bridge

I_Battery

112

Source Side H-Bridge

PI

+

I_ref

Battery Current Reference Generator

MPP of PV Array Battery Voltage

Figure 4. Control block diagram of DAB based Battery Charger.

114 115 116 117 118 119 120 121

When the battery current reference is zero, then the Gate pulses for source side and load side H-bridges will be in-phase to each other. During forward power flow i.e. for charging the battery, gate pulse of source side H-bridge will be in leading to the Gate pulse of load side H-Bridge. Similarly, during reverse power flow i.e. during battery discharging mode, load side gate pulse will be in leading. The amount of power transfer depends on the phase angle between Gate pulses for source side Bridge and Load side Bridge. As the size and cost of the high-frequency transformer are much lesser than that of a high-frequency transformer for the same power rating, Battery charger size and cost can be reduced by using a high-Frequency transformer in a DAB.

122

2.2 Control of Grid-Connected PV Inverter

123 124 125 126 127 128 129 130 131 132 133 134

A typical grid connected solar power conditioning system consists of three-phase two level PV-Inverter for converting DC power to AC power, a sine filter to smoothen the AC output and a Transformer to couple inverter and grid. The transformer also provides isolation between AC side and DC side. Figure 5 shows a control block diagram for a grid connected PV-Inverter. In this system, PV Array voltage and currents are to be monitored for MPP Tracking and the Grid voltage is to be monitored for Phase-locked Loop (PLL). The controller senses the charging current or discharging current of the battery and the MPP of PV Array then calculates the maximum possible power that can be fed to the Grid. Current reference is generated based on maximum possible Power and the PLL output. Three phase grid voltage is given to PLL to find out the angle wt. Angle wt obtained through PLL is used to generate Id and Iq components from Three phase grid currents. After comparing the Reference Idq currents and actual Idq currents, the error signals are given to PI controllers for the active and reactive power control. The PI controller outputs are converted back to

Energies 2016, 9, x FOR PEER REVIEW

135 136 137 138 139 140

5 of 14

Three Phase modulating signals and given to PWM Generator to generate Inverter gate pulses [8], [9]. In this work, a new power balancing control algorithm for the proposed configuration is developed and tested on the real controller with the help of Hardware-In-Loop simulations. The need of HIL Simulations, features of the Real-time digital simulator and the setup built for HIL simulation for the proposed configuration are explained in next section.

INVERTER

Gate

PLL

Vabc_Grid

Vabc

wt

PWM Id_Ref +

PI

DQ To ABC

Id_Grid

-

ABC To DQ

Iq_Ref +

PI

141

Iabc_Grid

Iq_Grid

-

Figure 5. Control block diagram of a Grid Connected PV Inverter

142 143

3 Hardware-In-Loop Simulation setup for the proposed system

144 145 146 147 148 149 150 151 152 153

In general, controller and control software are validated by integrating the controller with actual plant hardware. In the case of any error in the control system, there are risks of personal injuries, damage to the equipment and delays. Hardware-In-Loop (HIL) simulation is a useful tool to avoid such issues. In HIL simulation, instead of a real plant a mathematical model representing the plant loaded in the Real-time simulator to act like an actual Plant. Through HIL simulations, the response of controller in real time operation can be validated [10]. Following are the advantages with the HIL Simulation. (a) Preliminary controller software can be developed with minor assumptions in the plant parameters. (b) Once the Control parameters are calculated with HIL Simulation, it is easy to tune the parameters with the actual system. (c) Reduces the design cost and time (d) System protections in Real time can be analyzed by simulating faults.

S3

S5

Analog Output

S1

TRANSFORMER

Grid Switch

PV Voltage

Analog Input

FILTER

PV Switch

Controller Card

I/O Interface of RTDS

Simulated Power Circuit in Real Time Digital Simulator

PV Current Battery Voltage Battery Current Grid RYB Voltages Grid RYB Currents INV RYB Voltages BRC Input Voltage

S3

Battery Switch

Grid Switch ON/OFF Status

S4

LOAD SIDE H-BRIDGE

Inverter Start/Stop Command Battery Charger Start/ Stop Command Emergency Stop Command Inverter Stack Faulty Battery Charger Stack Faulty

Potentiometers Irradiance Grid Side Transformer Temperature Battery Charger Transformer Temperatue Inverter Stack Temperature Battery Charger Stack Temperature

Analog Input

156 157 158 159 160

ISOLATION TRANSFORMER

Gate Pulses for DAB

Battery Switch ON/OFF Status

Analog Input

SOURCE SIDE H-BRIDGE

154 155

S2

S4

Gate Pulses for Inverter

PV Switch ON/OFF Status

BATTERY S2

PV Switch On/OFF Command Battery Switch On/OFF Command Grid Switch On/OFF Command

Push Buttons

S1

S3

Digital Output

S2

Digital Input

S1

S6

Digital Input

GRID S4

Digital Output

PV Array

Figure 6. Block Diagram for HIL Simulation of the proposed Grid Energy storage system

To validate the control software for the proposed system, HIL simulations are carried out. The plant consists of PV array, Inverter, battery charger, isolation transformers, grid, battery and contactors are simulated in Matlab-Simulink. The simulated model is compiled and loaded in the processor of Real Time Digital Simulator (RTDS). Simulated Plant can be accessed by the external controller cards and other hardware through the I/O channels available in the RTDS. DSP based

Energies 2016, 9, x FOR PEER REVIEW

6 of 14

161 162 163 164 165

controller is connected as Hardware in the loop as shown in Figure 6. RTDS used for the HIL Simulations is Opal-RT make Simulator and the controller hardware is based on Texas make TMS320F2812 DSP based controller card. User interface panel consists of pushbuttons and Potentiometers (POT) is used for user commands and for simulating the faults. Figure 7 shows the Hardware setup for the HIL simulations.

166

3.1 Input-Output Channels of RTDS

167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200

Opal-RT make RTDS is equipped with Analog and Digital Input-Output modules. Voltage range for analog signals is +/- 15V whereas the voltage levels for Digital signals is Zero and +15V. 3.2 Input-Output Channels of Controller Card The controller used in this work is TMS320F2812 DSP processor based controller card. Voltage range for analog signals is +/- 10V whereas the voltage levels for Digital signals is Zero and +15V. 3.3 User Interface panel Signals The input to the simulated PV array is irradiance which can be given to the simulated plant through analog input channel of RTDS from a POT mounted on a user interface panel. The minimum value of POT output refers to the irradiance of Zero and the Maximum value of POT refers to 1000 W/Sq.m. From the user interface panel, Start Stop commands, Emergency stop commands are given to the controller card for the plant operations. Controller card receives temperature signals of isolation transformers and Power stacks from the user Interface panel. The possible fault signals are also given to the Controller card hence different faults can be simulated to check the functionality of controller and control algorithm. 3.4 Signals from Simulated Plant to Controller The controller receives the analog signals of the plant through analog output channels of the RTDS. The controller receives PV voltage and current signals which are required for tracking MPP. Battery voltage is required for finding out the charging current reference and battery current signal is required for closed loop current control of Battery charger. Three phase Grid voltage signals are required for PLL and inverter side voltages are monitored for synchronization purpose. Three phase inverter currents are required for closed loop current control of PV inverter. Based on the start-stop commands received from user Interface panel, the controller gives the ON/OFF Commands to PV Switch, Grid Switch and Battery switches through Digital Input channels of RTDS. Switch status outputs to the Controller are given to the controller through Digital Output channels of RTDS. 3.5 Online Plant parameter Modifications Online modification of simulated plant parameters i.e. Transformer parameters, filter parameters, Battery SOC, DC Link capacitor values and Load parameters etc. during the Real-time digital simulation is also possible through RT Lab main controller. Through online modifications, the optimum values of plant components can also be obtained.

Energies 2016, 9, x FOR PEER REVIEW

7 of 14

RTDS

CONTROLLER Power Supply

Push Buttons Potentiometers

201 202

Figure 7. HIL Simulation setup for the proposed Grid Energy storage system for PV Applications

203

4 Power Balancing Control of Grid Energy Storage System in PV applications

204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231

Power Control of PV with ESS for Off Grid applications is presented in [11]. In the system presented, Battery and PV arrays are connected to the common AC load through independent converters i.e. as an AC Centric system. During charging of the battery, PV array supplies power to the AC load and battery. When the battery is fully charged, battery and PV arrays supply power to the common AC Load. Conditions for battery charging and discharging and control of power converters during Mode-1 and Mode-2 operations are explained briefly. Experimental results were presented to show the dynamic response of the system during Mode changeover with Lead-Acid and Li-Ion Batteries. Control for high power PV + Fuel cell plant with hybrid energy storage consists of a battery and the super-capacitor is presented in [12]. Each energy source and energy storing element are connected to common DC link through independent converters in this configuration. Energy management among the different sources, control for charging super capacitor and batteries is explained briefly. Experimental results were presented for explaining the dynamic characteristics of system and plant performance during long load and Short load cycles. Since the system presented is for off-grid applications, Mode-3 operation i.e. charging the battery from Grid Supply is not covered in this work. Real-time simulation of the hybrid energy system with Wind-PV-Battery storage is presented in [13]. In the presented system, independent converters for Battery, PV modules, and Wind are used. Based on the power availability of all the sources, an algorithm is developed for battery charging, discharging and load shedding. The systems presented in [11], [12] and [13] are for Off-Grid Applications hence the control during Mode-3 of operation is not covered. System configurations presented in above works require independent converters for each source which may increase the cost of the system and also may increase the complexity of control algorithm. The above-mentioned drawbacks can be mitigated with the proposed system configuration and with the power balancing control algorithm explained in the next subsection. The proposed system is the combination of three phase PV inverter and a DAB based battery charger explained in section-2. Power flow through inverter can be controlled over a wide range through current control. Battery current can be controlled in both directions through DAB using a

Energies 2016, 9, x FOR PEER REVIEW

232 233 234 235 236 237 238 239 240 241 242

8 of 14

phase angle control. Power balancing among three sources in the presently proposed system is achieved by controlling the power flow through battery charger and inverter. Power balance control algorithm shown in Figure 8 is explained below. 1. Once the system is ready and Start command is given by the user, the controller reads the Gird voltages for determining wt through PLL. 2. Controller Initialize the value of Inverter reference current (Id_Inv_Ref) and Battery reference currents (I_Batt_Ref) as Zero. 3. Controller reads the PV voltage (Vpv), PV Current(Ipv), Battery voltage(VBatt) and Battery Current (I Batt) • If the PV voltage (Vpv) is less than Minimum PV voltage required (Vpv_Min) then MPP of PV Array is Zero.

243 244 245 246 247 248 249 250 251

o o o o

In this case, if the battery voltage is also less than the Nominal Battery Voltage Vb_Nominal then the system is in mode-3. In this mode, Battery needs to be charged but the PV array cannot give any power for battery charging. So the Grid shall supply the Power required for Battery charging. In this mode of operation, the Inverter acts like a simple Diode rectifier to provide DC Input to the Battery charger. Based on the SOC of battery, reference battery charging current I_Batt_Ref is obtained.

• If the PV voltage (Vpv) is more than Minimum PV voltage (Vpv_Min) then controller tracks the MPP of PV Array by monitoring PV voltage and current.

252 253

o

In case MPP is more than minimum value i.e. P_PV_Min then the system is in mode-1.

254 255

o

In this mode of operation, Battery will be in charging state and PV array gives the power for battery charging.

256

o

The remaining power after battery charging will be fed to the Grid.

257 258

o

Based on the SOC of Battery, reference battery charging current I_Batt_Ref is obtained.

259 260

o

Through Power balancing equation Inverter reference current Id_Inv_Ref is calculated based on MPP and Battery current.

• If the MPP is less than the minimum value (P_PV_Min) but the Battery is in charged condition then the system is in mode2.

261 262 263 264

o

In this case based on Backup time adjusted by the user, reference Battery current I_Batt_ref is calculated.

265 266

o

Through Power balancing equation Inverter reference current Id_Inv_Ref is calculated based on MPP and Battery current.

267 268

o

When PV voltage is more than Minimum DC Link Voltage, then Battery charger is operated with closed loop current control to maintain I_Batt = I_Batt_Ref.

269 270 271

o

When PV voltage is less than the minimum DC Link voltage then battery charger operates with closed loop voltage control to maintain a constant DC Link voltage i.e. Vdc_Link = Vdc_Link_Ref.

272 273 274 275

4.

After determining the Battery reference current I_Batt_Ref and Inverter reference current Id_Inv_ref, Controller implements the closed loop current control through PI controllers and releases the Gate pulses to Inverter stack and Battery charger stack.

Energies 2016, 9, x FOR PEER REVIEW

9 of 14 START

RESET FAULTS

NO

SYSTEM READY?

NO

START COMMAND?

YES

YES Initialize Id_Inv_Ref == 0 & I_Batt_Ref == 0

Measure Grid Voltage, Grid Currents, Battery Voltage, Battery Current, PV Array Voltage, PV Array Current

NO

Vpv > Vpv_Min ? YES

MPP == 0

Track MPP of PV Array

NO

NO

Battery Voltage > Vb_Nominal ?

MODE-2

Vpv > Vpv_Min ?

Vdc_Link_Ref = V_PV_Min

YES

Release Battery Charger Gate Pulses to maintain Vdc_Link = Vdc_Link_ref

Release Battery Charger Gate Pulses to maintain I_Batt = IBatt_Ref (As Shown in Fig. 4)

MODE-1

MODE-3

Determine Battery Dis-Charging Current Reference (I_Batt_Ref) based on Back up time required

(1) Block Gate Pulses to Inverter Stack

YES

YES

NO

(1)Determine Battery Charging Current Reference (I_Batt_Ref) based on SOC (2)Release Battery Charger Gate Pulses to maintain I_Batt = IBatt_Ref (As Shown in Fig. 4)

(3) Release Battery Charger Gate Pulses to maintain I_Batt = IBatt_Ref (As Shown in Fig. 4)

(2) Release Inverter Gate Pulses to maintain Id_Inv = Id_Inv_Ref (As Shown in Fig. 5)

YES FAULTS?

YES

STOP COMMAND?

CONTROL OF PV-INVERTER

(1) Calculate Active Component of Inverter Current Reference (Id_Inv_Ref) through Power Balancing equation Reference Inverter Power = MPP – (VBatt X I Batt_Ref) (I_Batt_Ref is Positive during Charging and Negative during Discharging)

(2) Find out Battery Charging Current (I_Batt_Ref) based on SOC

276 277

MPP > P_PV_Min ?

NO

NO

Figure 8. Algorithm for Power Balancing Control of Grid Energy Storage System in PV Applications

278

5 Results & Discussions

279

5.1 Inverter, Grid and Load Currents in different modes of Operation

280 281 282 283 284 285

Figure 9 shows the current waveforms in Mode-1 of operation. Since the PV array can produce more than the minimum power required for charging the battery and feeding internal loads connected to the plant, the additional power produced from the PV array is supplied to the Grid. An Irradiance of 1000 W/Sq.m is adjusted on the user interface panel; hence the PV array is producing the maximum possible power. From the presented result, it can be observed that the grid current is phase displaced by 180 degree to the inverter current.

Energies 2016, 9, x FOR PEER REVIEW

10 of 14

Inverter Current

Grid Current

Load Current

Line Voltage at PCC

286 287 288 289 290 291 292 293 294

Figure 9. Currents of Inverter, Grid, Load and voltage at PCC in Mode-1 of operation

In Mode-2 of Operation, an Irradiance of Zero W/Sq.m is adjusted on the user interface panel; hence the PV array cannot produce any power. The battery is in charged condition and supplies the power to the load based on the Ampere-Hour rating of the Battery and the discharging time or backup time adjusted by the user. Since the Local Loads consume more than the inverter supplied current, the remaining current is drawn from the Grid as shown in Figure 10. Since the load is drawing current from both the sources, the grid current and the inverter current are in phase with each other.

295 Inverter Current

Grid Current

Load Current

Line Voltage at PCC

296 297 298 299 300 301

Figure 10. Currents of Inverter, Grid, Load and voltage at PCC in Mode-2 of operation

In Mode-3 Operation, the PV Array cannot produce any power and the battery is in discharged condition. Since the Battery is to be charged, the Grid supplies the necessary charging current to the Battery and the current required for the Local Loads as shown in Figure 11.

Energies 2016, 9, x FOR PEER REVIEW

11 of 14

Inverter Current

Grid Current

Load Current

Line Voltage at PCC

302 303 304 305 306 307 308 309 310

Figure 11. Currents of Inverter, Grid, Load and voltage at PCC in Mode-3 of operation

The dynamic response of the system to a step change in inverter reference power is shown in Figure 12. When the inverter power reference is more than the local load requirement then the inverter is supplying current to grid and load. Since the grid is receiving the current, phase displacement is 180 degree between grid and inverter currents. After a step change in the reference power, since the reference power is less than the load requirement, the load current is supplied from both the inverter and the grid, hence the both the currents are in phase with each other. With the present controls, the system is coming to the steady state within one cycle time.

Inverter Current

Grid Current

Load Current

P_Inv_Ref > Pload

311 312

P_Inv_Ref < Pload

Figure 12. Currents of Inverter, Grid, Load for a step change in reference power.

313

5.2 Battery Charger Input and Output Currents in different modes of Operation

314 315 316 317 318 319 320

Battery Current is considered as positive during charging and Negative during Discharging of the Battery. The battery will be in charged Condition in Mode-1 and Mode-3 of operations as explained earlier. During charging, depending on the SOC of the battery, the charging current reference is obtained and the controller carries the closed loop current control of the battery charger. The battery Charger Input and Output currents for different modes of operation are discussed below. In mode-1 operation, since the battery is in charging condition, battery Current and the average value of Battery charger input current are positive as shown in Figure 13.

Energies 2016, 9, x FOR PEER REVIEW

12 of 14

Battery Charger Input Current

Battery Current

321 322 323 324 325 326 327 328 329

Figure 13. Battery Charger Input and output currents in Mode-1 operation

In Mode-2 of operation, when the PV array voltage is less than the minimum DC Link voltage then the battery charger operates with closed loop voltage control and maintains a constant DC Link voltage. The current through the battery depends on the Id Reference of the Inverter which is obtained through the Amp-Hour rating of the battery and the backup time required for the user. since the battery is in discharging condition, battery Current and the average value of Battery charger input current are negative as shown in Figure 14. Battery Charger Input Current

Battery Current

330 331 332 333 334

Figure 14. Battery Charger Input and output currents in Mode-2 operation

Similar to mode-1, in mode-3 operation also, battery Current and the average value of Battery charger input current are positive as shown in Figure 15. Charging current required for the battery is provided from grid supply in this case.

Energies 2016, 9, x FOR PEER REVIEW

13 of 14

Battery Charger Input Current

Battery Current

335 336 337 338 339

Figure 15. Battery Charger Input and output currents in Mode-3 operation

The dynamic response of the battery charger system is observed by applying a step change in the battery current reference. The system takes approximately 250 millisecond time to come to the steady state as shown in Figure 16.

Reference Battery Current

Actual Battery Current

340 341

Figure 16. Battery Charger reference and actual currents for a step change in reference current.

342

6 Conclusions

343 344 345 346 347 348 349 350 351 352

In this paper, a power balancing control for a grid energy storage system is presented. PBC technique is implemented on a TMS320F2812 processor based controller card and tested. Dynamic responses of the inverter and battery charger system are verified by applying a step change in the reference values. From the presented HIL results, it is observed that the performance of PBC control is satisfactory in all the three modes of operation and good dynamic performance is also achieved using this technique. As the controls are tested through HIL simulations in this work, plant parameters are considered as ideal whereas the plant parameters vary with operating temperatures in real time operation. Hence, minor modifications in plant parameters and tuning of control parameters are required to implement on the real system. The same system can be extended further to have the feature of reactive power compensation through the modified PBC control.

353

References

354 355 356 357

1. 2.

El Khateb, A.; Rahim, N. A.; Selvaraj ,J. Ćuk-Buck Converter for Standalone Photovoltaic System. Journal of Clean Energy Technologies 2013, vol 1(1), pp. 69-74. Wu, T.; Xiao, Q.; Wu, L.; Zhang, J. and Wang, M. Study and implementation on batteries charging method of Micro-Grid photovoltaic systems. Smart Grid and Renewable Energy 2011, vol 2(04), pp.324-329.

Energies 2016, 9, x FOR PEER REVIEW

358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398

3.

4. 5. 6. 7.

8.

9.

10.

11.

12.

13.

Choi, H.; Jang, M.; Ciobotaru, M.; Agelidis, V. G. Hybrid energy storage for large PV systems using bidirectional high-gain converters. IEEE International conference on Industrial Technology, 2016, pp.425-430. Shi, Y.; Li, R.; Xue, Y. and Li, H. Optimized operation of current-fed dual active bridge DC–DC converter for PV applications. IEEE Transactions on Industrial Electronics 2015, vol 62(11), pp.6986-6995. Bharathi, K. and Sasikumar, M. Voltage Compensation of Smart Grid using Bidirectional Intelligent Semiconductor Transformer and PV Cell. Indian Journal of Science and Technology 2016, vol 9(3). Jeong, D. K.; Kim, H. S.; Baek, J. W.; Kim, J. Y.; Kim, H. J. Dual active bridge converter for Energy Storage System in DC microgrid. IEEE Conference on Transportation Electrification Asia-Pacific, 2016, pp.152-156. Dutta, S.; Hazra, S.; Bhattacharya, S. A Digital Predictive Current-Mode Controller for a Single-Phase High-Frequency Transformer-Isolated Dual-Active Bridge DC-to-DC Converter. IEEE Transactions on Industrial Electronics 2016, vol 63(9), pp. 5943-5952. Kumar, N.; Saha, T. K.; Dey, J. Sliding-mode control of PWM dual inverter-based grid-connected PV system: modeling and performance analysis. IEEE Journal of Emerging and Selected Topics in Power Electronics 2016, vol 4(2), pp. 435-444. Toodeji, H.; Farokhnia, N.; Riahy, G. H. Integration of PV module and STATCOM to extract maximum power from PV. IEEE International Conference on Electric Power and Energy Conversion Systems, 2009, pp.1-6. Lemaire, M.; Sicard, P.; Belanger, J. Prototyping and Testing Power Electronics Systems Using Controller Hardware-In-the-Loop (HIL) and Power Hardware-In-the-Loop (PHIL) Simulations. IEEE international conference on Vehicle Power and Propulsion, 2015, pp.1-6. Serban, E.; Ordonez, M.; Pondiche, C.; Feng, K.; Anun, M.; Servati, P. Power management control strategy in photovoltaic and energy storage for off-grid power systems. IEEE International conference on Power Electronics for Distributed Generation Systems, 2016, pp.1-8. Sikkabut, S.; Mungporn, P.; Ekkaravarodome, C.; Bizon, N.; Tricoli, P.; Nahid-Mobarakeh, B.; Thounthong, P. Control of High-Energy High-Power Densities Storage Devices by Li-ion Battery and Supercapacitor for Fuel Cell/Photovoltaic Hybrid Power Plant for Autonomous System Applications. IEEE Transactions on Industry Applications 2016, vol 52(5), pp. 4395-4407. Merabet, A.; Ahmed, K. T.; Ibrahim, H.; Beguenane, R.; Ghias, A. M. Energy Management and Control System for Laboratory Scale Microgrid Based Wind-PV-Battery. IEEE Transactions on Sustainable Energy 2017, vol 8(1), pp. 145-154.

Acknowledgments: No funding resources Author Contributions: Sridhar Vavilapalli, Sanjeevikumar Padmanaban, Umashankar Subramaniam, has developed the original proposed ac power research work and implemented in real-time hardware RTDS HIL simulation system. Furthermore, Sanjeevikumar Padmanaban, Lucian Mihet-Popa had supported for the insight, technical expertise to make the work quality in its production and validation with theoretical concepts. All authors contributed involved in each part of the article for its final depiction as research paper work”. Conflicts of Interest: The authors declare no conflict of interest.

399 400 401 402

14 of 14

© 2016 by the authors. Submitted for possible open access publication under the terms and conditions of the Creative Commons Attribution (CC-BY) license (http://creativecommons.org/licenses/by/4.0/).